The following P-Q data points (shown in Table 1) are obtained from the manufacturer's
static pressure curve for a single fan unit at 750 rpm and a density of 1.2 kg/m3. The speed is
to be increased to 850 rpm, the density changes to 1.16 kg/m3 and two fans are to be
operated in parallel.
Table 1
Quantity(
ms) 100
155
190
212
Pressure (Pa)
235
250
2000
1500
1050
500
0
Calculate the corrected single fan curve at 850 rpm and a density of 1.16 kg/m^3?β