A 230 V, single-phase supply feeds the following loads: (a) incandescent lamps taking a current

of 6 A at unity power factor; (b) fluorescent lamps taking a current of 5 A at 0.75 leading power

factor; (c) a motor taking a current of 7 A at 0.7 lagging power factor. You are required to

correct the power factor to unity.

a) Show how it can be achieved by connecting a parallel reactance to the load

- provide the phasor diagram based on computed branch currents; and the power

triangles before and after power factor correction.

- provide the appropriate kVar rating of reactance, and if it’s a capacitor bank compute

the capacitance or if it’s an reactor (inductor) compute the inductance.

b) If it is proposed to use series reactance to perform power factor correction, show how this

can be achieved and comment on this approach.

d) Verify your answers using Matlab/Simulink

- show the rms currents on the Simulink model

- Plot the instantaneous branch currents and show clearly how the phase angle between

the supply voltage and supply current changes, accordingly

ansver
Answers: 1

Another question on Engineering

question
Engineering, 04.07.2019 18:10
Aloaded platform of total mass 500 kg is supported by a dashpot and by a set of springs of effective stiffness 72 kn/m. it is observed that when the platform is depressed through a distance x = 12.5 cm below its equilibrium position and then released without any initial velocity; it reaches its equilibrium position in the shortest possible time without overshoot. find the position and velocity of the loaded platform 0.10 sec. after its release. if a further load of 400 kg is added to the platform, find, i) the frequency of damped vibrations, and i) the amplitude of vibration after 2 complete oscillations, given that the initial amplitude is 15 cm.
Answers: 1
question
Engineering, 04.07.2019 18:10
Items are similar to the free issue items, but their access is limited. (clo5) a)-bin stock items free issue b)-bin stock controlled issue c)-critical or insurance spares d)-rebuildable spares e)-consumables
Answers: 1
question
Engineering, 04.07.2019 18:20
Inadequate stores control is not an obstacle to effective work order system. (clo4) a)-true b)-false
Answers: 3
question
Engineering, 04.07.2019 18:20
Modern high speed trains do not have perpendicular expansion gaps where rails are joined end-to-end any more they are mostly welded together but what might happen if there was a spell of particularly hot weather that causes inspection of the tracks?
Answers: 1
You know the right answer?
A 230 V, single-phase supply feeds the following loads: (a) incandescent lamps taking a current
Questions
question
Mathematics, 30.12.2020 08:00
question
Mathematics, 30.12.2020 08:10
question
Mathematics, 30.12.2020 08:10
question
Mathematics, 30.12.2020 08:10
Questions on the website: 13722360