A municipal water system requires an effluent chlorine residual of 0.15 mg/L. The chlorine demand placed upon the system is 0.45 mg/L, and the treatment plant processes a daily water flow of 15,000,000 gal.
The chlorine required is most nearly:

A) 17 kg/d B) 26 kg/d C) 34ka/d D) 43 kg/d

ansver
Answers: 1

Another question on Engineering

question
Engineering, 04.07.2019 18:10
The mass flow rate of the fluid remains constant in all steady flow process. a)- true b)- false
Answers: 1
question
Engineering, 04.07.2019 18:10
An air conditioning system consist of a 5 cm diameter pipe, operating at a pressure of 200 kpa. the air initially enters the pipe at 15°c with a velocity of 20 m/s and relative humidity of 80%. if the heat supply throughout the process is 960 w, determine the relative humidity and the temperature at the outlet